ADL-ADU – Advantage

SPACE-RAY  Tube heaters have many applications from factories and warehouses to sports halls, aircraft hangars, supermarkets, exhibition halls and retail premises. So no matter what the use, size or shape of your building you can rest assured that SPACE-RAY Radiant Tube heaters will suit your needs.

How do SPACE-RAY Radiant Tube heaters work? A gas fired flame within the Calorised Emitter Tube causes the heat to radiate invisible “black heat” energy. This energy gently warms surfaces and people without heating the air directly. Therefore SPACE-RAY Radiant Tube Heaters are highly fuel efficient and are an ideal total heating system or for zone/spot heating.

Need to ask a question? Call Us: + 44 (0) 1473 830 551

Features

  • 5 Year emitter tube guarantee
  • Calorised Emitter Tube - Highly efficient
  • Calorised Emitter Tube - flake-free - guaranteed
  • Lightweight construction - 4" tubes supplied in 3m sections - easy to assemble and fit
  • Double Aluminium radiant reflectors - the proven superior material to maximise downward heat
  • All units individually tested before despatch
  • Made in the UK under ISO 9001:2008 quality assured
  • CE marked for both Natural Gas and LPG

ADU

  ADU25 ADU30 ADU35 ADU40 ADU45
Technical Specification
Input – kW 23.0 29.20 34.50 42.20 47.0
Length -mm 5385mm 5510mm 6970mm
Width -mm 460mm 715mm
Height -mm 175mm 210mm
Weight – KG 47kg 66kg 81kg
Gas Connection All Models R -1/2
Supply Pressure Natural Gas – Min 17mbar, Max 25mbar; Propane – Min 25mbar, Max 45mbar; Butane – Min 20mbar, Max 35mbar
Electrical Supply 230v~50Hz 125w, Current rating at 0.55A, Fuse externally 3A
Flue Diameter All models – 100mm
Air Inlet Connection All Models – 101.6mm
Mounting Height
Horizontal 3.0m – 8.0m 3.8m – 10.0m 4.0m – 12.5m 4.8m – 13.5m 5.6m – 15m
Angle > 30 Degrees 2.7m – 5.0m 3.3m – 7.0m 3.7m – 8.0m 4.0m – 9.0m 4.8m – 11m
Minimum Clearances To Combustible Materials – mm
Side 510 760
Above 450 610
Below 1220 2285
End 510 610
Front 610 760
Rear 305 380

 

ADL

  ADL25 ADL30 ADL35 ADL40 ADL45
Technical Specification
Input – kW 23.0 29.20 34.50 42.20 47.0
Length -mm 10065mm 9955mm 13000mm
Width -mm 340mm
Height -mm 180mm
Weight – KG 46kg 62kg 79kg
Gas Connection All Models R -1/2
Supply Pressure Natural Gas – Min 17mbar, Max 25mbar; Propane – Min 25mbar, Max 45mbar; Butane – Min 20mbar, Max 35mbar
Electrical Supply 230v~50Hz 125w, Current rating at 0.55A, Fuse externally 3A
Flue Diameter 100mm
Air Inlet Connection 101.6mm
Mounting Height
Horizontal 3.0m – 8.0m 3.8m – 10.0m 4.0m – 12.5m 4.8m – 13.5m 5.6m-15m
Angle > 30 Degrees 2.7m – 5.0m 3.3m – 7.0m 3.7m – 8.0m 4.0m – 9.0m 4.8m-11m
Minimum Clearances To Combustible Materials – mm
Side 510 760
Above 450 610
Below 1220 2285
End 510 610
Front 610 760
Rear 305 380