EPA-L

SPACE-RAY Linear Tube heaters have many applications from factories and warehouses to sports halls, aircraft hangars, supermarkets, exhibition halls and retail premises. So no matter what the use, size or shape of your building you can rest assured that SPACE-RAY Radiant Tube heaters will suit your needs.

How do SPACE-RAY Radiant Tube heaters work? A gas fired flame within the Calorised Emitter Tube causes the heat to radiate invisible “black heat” energy. This energy gently warms surfaces and people without heating the air directly. Therefore SPACE-RAY Radiant Tube Heaters are highly fuel efficient and are an ideal total heating system or for zone/spot heating.

Need to ask a question? Call Us: + 44 (0) 1473 830 551

Features

  • Part L 2010 & EcoDesign Compliant
  • Eight model ratings: 12kW to 55kW available in Linear and 'U' models
  • Single Stage and Two Stage Modulating Inputs available
  • Push Through System (Positive Pressure)
  • Tube Integrity Safety System (TISS™)
  • Blower motor totally enclosed in the burner box.
  • 5 Year emitter tube guarantee
  • Calorised Emitter Tube - Highly efficient
  • Calorised Emitter Tube - flake-free - guaranteed
  • Lightweight construction - 4" tubes supplied in 3m sections - easy to assemble and fit
  • Aluminium radiant reflectors - the proven superior material to maximise downward heat
  • All units individually tested before despatch
  • Made in the UK under ISO 9001:2008 quality assured system
  • CE marked for both Natural Gas and LPG
EPA L 12 EPA L 15 EPA L 20 EPA L 25 EPA L 30 EPA L 38 EPA L 45 EPA L 55
Technical Specification
Input – kW 11.5 15 20 25 30 37 45 53
Input – kW – 2 Stage 8.1 10.5 14 17.5 21 25.9 31.5 37.1
Length – m 4.93 – 6.46 6.46 – 12.55 9.5 – 12.55 12.55 – 18.65 15.6 – 21.7
Width -mm 330
Height -mm 370
Gas Connection All Models R -1/2
Supply Pressure Natural Gas – G20 20mbar Propane – G31 37mbar
Electrical Supply 230v~50Hz 90w, Current rating 0.39A, Fuse externally 3A
Flue Diameter 100mm Dia.
Air Inlet Connection 101.6mm Dia.
Mounting Height
Horizontal 2.4m – 6.0m 3.0m – 8.0m 3.8m – 10.0m 4.0m – 12.5m 5.6m-15m 6.0m-15m
Angle > 30 Degrees 2.1m – 4.5m 2.7m – 5.0m 3.3m – 7.0m 3.7m – 8.0m 4.8m-11m 5.2m-11m
Minimum Clearances To Combustibles
Side mm 560 710 860 1060
Above mm 150
Below mm 1320 1420 1520 1780 1930 2060 2180
End mm 380 510
Front mm 1020 1220 1320 1470 1680 1780 1910
Rear mm 300