GIRAD Continuous Radiant Tube Heater

Need to ask a question? Call Us: + 44 (0) 1473 830 551
Features
- Bespoke designed radiant heating system for efficient, cost saving heating and coverage of large floor areas
- Burner located outside of space being heated
- Single point of service. No parts within the space require servicing
- Efficient modulating burner
- Significant installation savings compared to multi-burner systems
- Flexible layout with up to 324m tube run (model dependent)
- Patented ECOMIX burner with turndown ratio of up to 10:1
- Recirculated flues gases reduce NOX emissions
- Optional CD condenser module for insertion in flue system to recover otherwise wasted energy
- Fan & burner mounted outside of space, therefore no component noise
| SPECIFICATION GUIDE – GSR Range | ||||||||||
| Models | GSR50.1A GSR50.1H | GSR100.2H | GSR100.1A GSR100.1H | GSR100.1EA GSR100.1EH | GSR150A GSR150H | GSR200.1A GSR200.1H | GSR200.2H | GSR300.1A GSR300.1H | ||
| Thermal capacity | Maximum (kW) | 50 | 100 | 100 | 115 | 150 | 200 | 200 | 300 | |
| Minimum (kW) | 35 | 70 | 70 | 90 | 120 | 140 | 140 | 210 | ||
| Thermal efficiency1 | % (ncv) | 94 96 | 96 | 94 96 | 95 96 | 95 96 | 95 96 | 96 | 95 97 | |
| Gas connection | BSP | ½” | ¾” | ¾” | 1¼” | 1¼” | 1¼” | 1½” | 1¼” | |
| Max gas consumption | Nat Gas G20 (m3/h) | 4.8 | 9.5 | 9.5 | 11.0 | 14.3 | 19.1 | 19.1 | 28.6 | |
| LPG G30 (kg/h) | 3.6 | 7.1 | 7.1 | 8.2 | 10.7 | 14.3 | 14.3 | 21.4 | ||
| Flue connection OD Ø | (mm) | 104 | 144 | 144 | 144 | 144 | 205 | 205 | 250 | |
| Radiant tube Ø | (mm) | 200 | 200 | 300 | 300 | 300 | 300 | 300 | 300 | |
| Circuit length Ø200mm Single pipe system2 | Maximum (m) | 72 | 90 | – | – | – | – | – | – | |
| Minimum (m) | 42 | 54 | – | – | – | – | – | – | ||
| Circuit length Ø200mm Twin pipe system2 | Maximum (m) | 36 | 45 | – | – | – | – | – | – | |
| Minimum (m) | 21 | 27 | – | – | – | – | – | – | ||
| Circuit length Ø300mm Single pipe system2 | Maximum (m) | – | – | 150 | 156 | 168 | 234 | 234 | 324 | |
| Minimum (m) | – | – | 54 | 60 | 76 | 102 | 102 | 156 | ||
| Circuit length Ø300mm Single pipe system2 | Maximum (m) | – | – | 75 | 78 | 84 | 117 | 117 | 162 | |
| Minimum (m) | – | – | 27 | 30 | 38 | 51 | 50 | 78 | ||
| Electrical supply | 230v 1 Phase 50 Hz | 415v 3 Phase 50 Hz | ||||||||
| Max electrical consumption (A) | 2.2 | 8.5 | 4.8 | 4.8 | 4.8 | 4.8 | 4.6 | 4.6 | ||
| Burner module weight | (Kg) | 88 | 96 | 115 | 119 | 119 | 127 | 165 | 173 | |
| Max weight of radiant tube assembly Ø200mm per m | Single pipe system (kg) | 16 | 16 | – | – | – | – | – | – | |
| Twin pipe system (kg) | 19 | 19 | – | – | – | – | – | – | ||
| Max weight of radiant tube assembly Ø300mm per m | Single pipe system (kg) | – | – | 18 | 18 | 18 | 18 | 18 | 18 | |
| Twin pipe system (kg) | – | – | 25 | 25 | 25 | 25 | 25 | 25 | ||
| SPECIFICATION GUIDE – GSR Range – With Condensor Module | |||||||||
| Models | GSR100.2HC | GSR100.1HC | GSR100.1EHC | GSR150HC | GSR200.1HC | GSR200.2HC | GSR300.1HC | ||
| Thermal capacity | Maximum (kW) | 100 | 100 | 115 | 150 | 200 | 200 | 300 | |
| Minimum (kW) | 70 | 70 | 90 | 120 | 140 | 140 | 210 | ||
| Thermal efficiency1 | % (ncv) | 104.5 | 104.5 | 104.5 | 104.5 | 104.5 | 104.5 | 104.5 | |
| Gas connection | BSP | ¾” | ¾” | 1¼” | 1¼” | 1¼” | 1¼” | 1½” | |
| Max gas consumption | Nat Gas G20 (m3/h) | 9.5 | 9.5 | 11.0 | 14.3 | 19.1 | 19.1 | 28.8 | |
| LPG G30 (kg/h) | 7.1 | 7.1 | 8.2 | 8.6 | 13.3 | 13.3 | 21.4 | ||
| Flue connection OD Ø | (mm) | 200 | 200 | 200 | 200 | 200 | 200 | 200 | |
| Radiant tube Ø | (mm) | 200 | 300 | 300 | 300 | 300 | 300 | 300 | |
| Circuit length Ø200mm Single pipe system2 | Maximum (m) | 90 | – | – | – | – | – | – | |
| Minimum (m) | 54 | – | – | – | – | – | – | ||
| Circuit length Ø200mm Twin pipe system2 | Maximum (m) | 45 | – | – | – | – | – | – | |
| Minimum (m) | 27 | – | – | – | – | – | – | ||
| Circuit length Ø300mm Single pipe system2 | Maximum (m) | – | 150 | 156 | 168 | 234 | 234 | 324 | |
| Minimum (m) | – | 54 | 60 | 76 | 102 | 102 | 156 | ||
| Circuit length Ø300mm Single pipe system2 | Maximum (m) | – | 75 | 78 | 84 | 117 | 117 | 162 | |
| Minimum (m) | – | 27 | 30 | 38 | 51 | 51 | 78 | ||
| Electrical supply | 230v 1 Phase 50 Hz | 415v 3 Phase 50 Hz | |||||||
| Max electrical consumption (A) | 6 | 8.6 | 8.6 | 8.6 | 8.6 | 8.4 | 8.4 | ||
| Burner module weight | (Kg) | 191 | 210 | 214 | 214 | 257 | 280 | 303 | |
| Max weight of radiant tube assembly Ø200mm per m | Single pipe system (kg) | 16 | – | – | – | – | – | – | |
| Twin pipe system (kg) | 19 | – | – | – | – | – | – | ||
| Max weight of radiant tube assembly Ø300mm per m | Single pipe system (kg) | – | 18 | 18 | 18 | 18 | 18 | 18 | |
| Twin pipe system (kg) | – | 25 | 25 | 25 | 25 | 25 | 25 | ||