SRC

SPACE-RAY SRC Low Intensity Continuous Radiant Heating Systems have many applications from factories and warehouses to sports halls, aircraft hangars, supermarkets, exhibition halls and retail premises. So no matter what the use, size or shape of your building you can rest assured that SPACE-RAY SRC Low Intensity Continuous Radiant Heating Systems will suit your needs.

How do SPACE-RAY Radiant Tube heaters work? A gas fired flame within the Calorised Emitter Tube causes the heat to radiate invisible “black heat” energy. This energy gently warms surfaces and people without heating the air directly. Therefore SPACE-RAY Radiant Tube Heaters are highly fuel efficient and are an ideal total heating system or for zone/spot heating.

 

Need to ask a question? Call Us: + 44 (0) 1473 830 551

Features

  • Bespoke designed radiant heating system for efficient, cost saving heating and coverage of large floor areas
  • Multiple burners can be linked together to a single, common extraction fan and flue
  • Pre-mix burners for efficient stoichiometric combustion
  • Multiple systems can be designed to heat the largest industrial, commercial or leisure complexes
  • In addition you get all the benefits and advantages of SPACE-RAY quality
  • 5 Year emitter tube guarantee
  • Calorised Emitter Tube - Highly efficient
  • Calorised Emitter Tube - flake-free - guaranteed
  • Aluminium radiant reflectors - the proven superior material to maximise downward heat
  • All units individually tested before despatch
  • Made in the UK under ISO 9001:2008 quality assured system
  • CE marked for both Natural Gas and LPG
Model SRC12 SRC18 SRC24 SRC32 SRC38 SRC46 SRC24M SRC32M SRC38M SRC46M
Nominal gross heat input kW 12 18 24 32 38 46
Nominal gross heat input range kW 24/12 32/16 38/19 46/23
Gas Consumption
Natural Gas G20 m3/h 1.14 1.72 2.29 3.05 3.62 4.38 2.29 3.05 3.62 4.38
Propane G31 m3/h 0.45 0.68 0.9 1.21 1.43 1.73 0.9 1.21 1.43 1.73
Inlet gas pressure (mbar) Max 50
Min 17.5
Radiant Tube Length (m) (Distance between burners) Max 7.2 10.2 13.1 18 23 27 13.1 18 23 27
Min 5.2 7.4 9.4 14 18 23 9.4 14 18 23
m Max
Max tube temp OC 450 450 450 480 480 480 450 480 480 480
Max burners per branch 5 4 3
Electrical supply 230 volts 1 phase 50Hz
Current rating 0.05 amps max (inductive)
Distance From Combustibles (mm)
Below Tube End vent/inline
Without undershield

1120/1250

1440/1700 1570/2100 1700/2100 1120/1250 1440/1700 1570/2100 1700/2100
With undershield 760/850 785/1050 850/1050 760/850 785/1050 850/1050
Above Tube 250
Horizontally
Standard Reflector 600/770 700/850 700/1000 600/770 700/850 700/1000
Perimeter Reflector 305/450 305/510 305/600 305/450 305/510 305/600
Minimum mounting height m 3 3.6 4 4.7 5.3 6 4 4.7 5.3 6
Average weight kg/m 10

 

Documents