LRL-LRU

SPACE-RAY  Tube heaters have many applications from factories and warehouses to sports halls, aircraft hangars, supermarkets, exhibition halls and retail premises. So no matter what the use, size or shape of your building you can rest assured that SPACE-RAY Radiant Tube heaters will suit your needs.

How do SPACE-RAY Radiant Tube heaters work? A gas fired flame within the Calorised Emitter Tube causes the heat to radiate invisible “black heat” energy. This energy gently warms surfaces and people without heating the air directly. Therefore SPACE-RAY Radiant Tube Heaters are highly fuel efficient and are an ideal total heating system or for zone/spot heating.

 

Need to ask a question? Call Us: + 44 (0) 1473 830 551

Features

  • Year emitter tube guarantee
  • Calorised Emitter Tube - Highly efficient
  • Calorised Emitter Tube - flake-free - guaranteed
  • Lightweight construction - 4" tubes supplied in 3m sections - easy to assemble and fit
  • Aluminium radiant reflectors - the proven superior material to maximise downward heat
  • All units individually tested before dispatch
  • Made in the UK under ISO 9001:2008 quality assured system
  • CE marked for both Natural Gas and LPG
  LRU15 LRU25
Technical Specification
Input – kW 15.0 23.0
Length -mm 3100mm 5385mm
Width -mm 460mm
Height -mm 175mm
Weight – KG 31kg 47kg
Gas Connection All Models R -1/2
Supply Pressure Natural Gas – Min 17mbar, Max 25mbar; Propane – Min 25mbar, Max 45mbar; Butane – Min 20mbar, Max 35mbar
Electrical Supply 230v~50Hz 125w, Current rating at 0.55A, Fuse externally 3A
Flue Diameter All models – 100mm
Air Inlet Connection All Models – 101.6mm
Mounting Height
Horizontal 2.4m – 6.0m 3.0m – 8.0m
Angle > 30 Degrees 2.1m – 4.5m 2.7m – 5.0m
Minimum Clearances To Combustibles – mm
Side 450 510
Above 450
Below 1220
End 450 510
Front 575 610
Rear 305

 

  LRL15 LRL25
Technical Specification
Input – kW 15.0 23.0
Length -mm 5493 mm 10065mm
Width -mm 340mm
Height -mm 180mm
Weight – KG 33kg 46kg
Gas Connection All Models R -1/2
Supply Pressure Natural Gas – Min 17mbar, Max 25mbar; Propane – Min 25mbar, Max 45mbar; Butane – Min 20mbar, Max 35mbar
Electrical Supply 230v~50Hz 125w, Current rating at 0.55A, Fuse externally 3A
Flue Diameter 100mm
Air Inlet Connection 101.6mm
Mounting Height
Horizontal 2.4m – 6.0m 3.0m – 8.0m
Angle > 30 Degrees 2.1m – 4.5m 2.7m – 5.0m
Minimum Clearances To Combustibles – mm
Side 450 510
Above 450
Below 1220
End 450 510
Front 575 610
Rear 305